| 2017-03-17 17:12:22 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. DISREGARD SIGNATURE REVIEWS #1 AND #2; OUR SYSTEM |
| | WAS EXPERIENCING GLITCHES AT THE TIME THE REVIEWS WERE |
| | ENTERED AND ARE NOW LOCKED AND CANNOT BE UPDATED OR |
| | EDITED. THEREFORE A 3RD REVIEW WAS OPENED. |
| | |
| | 2. THE MAJORITY OF THE PAGES ARE "CERTIFIED" RATHER |
| | THAN SIGNED AND SEALED. FOR EXAMPLES, SEE THE CHANNEL |
| | LETTER SIGN PLANS; THEY HAVE A TYPICAL COMPLIANT |
| | DIGITAL SIGNATURE AND SEAL. OTHER PAGES ARE "CERTIFIED" |
| | AND DO NOT INCLUDE A SIGNATURE. IT IS NOT CLEAR IF THIS |
| | METHOD COMPLIES WITH FS471. OBTAIN VERIFICATION FROM |
| | FBPE OR THE ISSUER OF THE DIGITAL SIGNATURE/SEAL THAT |
| | THIS IS ACCEPTABLE IN LIEU OF A DIGITAL SEAL WITH |
| | SIGNATURE. |
| | |
| | IF APPLICANT DOES NOT UNDERSTAND THIS COMMENT, PLEASE |
| | SEE ANY SHEET OTHER THAN THE CHANNEL LETTER PAGES. THE |
| | CHANNEL LETTER PAGES ARE SIGNED AND SEALED, THE OTHER |
| | PAGES ARE CERTIFIED. |
| | |
| | 3. A CERTIFIED PAGE WAS SENT TO FBPE TO VERIFY THAT |
| | THIS WAS ACCEPTABLE IN LIEU OF A DIGITAL SIGNATURE AND |
| | SEAL. I HAVE NOT RECEIVED A RESPONSE REGARDING THIS |
| | ISSUE, BUT WAS INFORMED THAT AN IMAGE OF A SIGNATURE IS |
| | NOT ACCEPTABLE. EITHER REMOVE FROM ALL PAGES OR HAVE |
| | FBPE EMAIL A STATEMENT THAT THIS IS ACCEPTABLE TO THEM. |
| | SEE FS471, FAC61G15-23.002, 003. |
| | |
| | |
| | |