| Plan Review Notes For Permit 17030199 |
| Permit Number |
17030199 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-08 13:24:49 | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE | | | POOL HEATER. THE HEATER SHALL BE LISTED AND LABELED PER | | | THE 2014 FBC-FUEL GAS SEC.301.3 IF THE HEATER IS A GAS | | | HEATER. | | | .2) INDICATE THE BTU LOAD AND MODEL OF THE UNIT ON THE | | | REQUESTED MANUFACTURER'S SPECIFICATION SHEETS. | | | 3) THE POOL HEATER SHALL MEET THE MINIMUM EFFICIENCY | | | LISTED IN 2014 FBC-ENERGY TABLE C404.2. | | | 4) THE POOL HEATER SHALL COMPLY WITH 2014 FBC-ENERGY | | | SEC. C404.7.2.(TIME SWITCHES). | | | 5) IF THE POOL HEATER IS GAS, A POOL CONTRACTOR CANNOT | | | CONNECT THE GAS LINES TO THE HEATER. A SEPARATE PERMIT | | | SHALL BE SUBMITTED AND ISSUED TO EITHER A PLUMBING | | | CONTRACTOR OR A GAS CONTRACTOR. FL. STATUTE 489.105. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|