| 2017-03-07 10:57:51 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PLEASE SUBMIT A REVISED LOAD CALCULATION FOR NEW | | | 50AMP SHOWN FED FROM 400AMP SERVICE | | | 2. NOTE THAT MODIFICATION DONE TO ELECTRICAL SERVICE | | | WILL REQUIRE A REVISED FAULT CURRENT CALCULATION AT | | | SERVICE PER NEC 110.24B. A NOTE WILL SUFFICE. | | | 3. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | | | | | | | | | | |
|