Plan Review Notes
Plan Review Notes For Permit 17030121
Permit Number 17030121
Review Stop M
Sequence Number 1
Notes
Date Text
2017-03-10 15:39:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030121
 3/10/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE A VENTILATION CALCULATION FOR THE NEW
 RECONFIGURED RADIOLOGY ROOM PER TABLE 403.3 FBC-14
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) REFER TO TABLE 7-1 ASHRAE 170 AND PROVIDE THE DESIGN
 PARAMETERS FOR THE RADIOLOGY ROOM.
  
 3) M2.03: PROVIDE FIRE DAMPERS FOR THE DUCTS
 PENETRATING THE FIRE-RATED RADIOLOGY/CORRIDOR WALL.
  
 4) M0.00: PROVIDE THE CORRECT PROJECT DESIGN CRITERIA
 FOR WEST PALM BEACH FL. THE CRITERIA ON THE PLAN IS FOR
 MIAMI.
  