| 2017-03-28 13:06:50 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | THE PANEL SCHEDULES AND RISER PLANS DO NOT SEEM TO | | | CORRESPOND. THE SPECIFICATIONS AND LOADS FOR THE NEW | | | EQUIPMENT HAVE NOT BEEN ADEQUATELY IDENTIFIED. NEC | | | 215.5 | | | | | | VERIFY THE NEW RADIOLOGY EQUIPMENT HAS BEEN LISTED FOR | | | USE AND IS IN CONFORMITY WITH THE REQUIREMENTS OF THE | | | NATIONAL ELECTRICAL CODE. NEC 110.3 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6654 | | | 561-373-3701 | | | [email protected] | | | |
|