2017-03-17 09:32:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17030121
 ADD: 1309 N. FLAGLER DR. X-RAY ROOM : T3177
 CONT: PM WRIGHT
 TEL: 561-309-6162
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 17/ 2017
 ACTION: BUILDING PROVISO
  
 1) DEFERRED SUBMITTAL 107.3.4.2. SHEET A1.0 SPECIFIC
 FLOOR PLAN NOTE # 4, INDICATES THE INSTALLATION OF NEW
 5/8 INCH LEAD LINED DRYWALL WITH 1/8TH INCH THICK LEAD
 LINING OVER THE EXISTING WALLS AS REQUIRED OR DIRECTED
 BY THE RADIATION CONSULTANT / PHYSICIST. 2014 FBC-B
 465.5.1 SHIELDING. 465.5.1.2
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED. 465.5.1.3. PRIOR TO CONSTRUCTION, THE FLOOR
 PLANS AND EQUIPMENT ARRANGEMENT OF ALL NEW
 INSTALLATIONS, OR MODIFICATIONS OF EXISTING
 INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND
 ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE
 SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND
 APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER
 REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE
 FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
 SHOP DRAWING REVIEW AND APPROVAL BY THE DESIGNER OF
 RECORD BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC..
  
 2) DEFERRED SUBMITTAL 107.3.4.2. SHEET S1 & S2 DRAWINGS
 BY GE HEALTHCARE. SHOW THE USE OF UNISTRUT SUPPORT AND
 EQUIPMENT TO BE HUNG FROM THE CEILING. SUBMIT SHOP
 DRAWINGS TO THE DESIGNER OF RECORD SHOWING THE
 ALLOWABLE AMOUNT OF LBS. TO BE HUNG FROM THE ASSEMBLY.
 SHOW THE ATTACHMENT TO THE STRUCTURAL STEEL OR THROUGH
 BOLT THROUGH CONCRETE FLOOR SHOULD BE FAVORED. DO NOT
 USE ANCHORS IN DIRECT TENSION. NOTE IF THE SHOP
 DRAWINGS WERE PREPARED BY AN ENGINEER, THEY WILL NEED
 TO BE SIGNED AND SEALED. FL ADMIN CODE 61G15-23.002
 ENGINEERS. SINCE THE GE HEALTHCARE DRAWINGS ARE NOT
 SIGNED AND SEALED THE SHOP DRAWINGS BEING SUBMITTED
 WILL NEED TO BE REVIEWED AND APPROVED BY THE DESIGNER
 OF RECORD BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER