| 2017-03-17 09:32:10 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17030121 |
| | ADD: 1309 N. FLAGLER DR. X-RAY ROOM : T3177 |
| | CONT: PM WRIGHT |
| | TEL: 561-309-6162 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MARCH 17/ 2017 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) DEFERRED SUBMITTAL 107.3.4.2. SHEET A1.0 SPECIFIC |
| | FLOOR PLAN NOTE # 4, INDICATES THE INSTALLATION OF NEW |
| | 5/8 INCH LEAD LINED DRYWALL WITH 1/8TH INCH THICK LEAD |
| | LINING OVER THE EXISTING WALLS AS REQUIRED OR DIRECTED |
| | BY THE RADIATION CONSULTANT / PHYSICIST. 2014 FBC-B |
| | 465.5.1 SHIELDING. 465.5.1.2 |
| | DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL |
| | HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT |
| | REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE |
| | INSTALLED. 465.5.1.3. PRIOR TO CONSTRUCTION, THE FLOOR |
| | PLANS AND EQUIPMENT ARRANGEMENT OF ALL NEW |
| | INSTALLATIONS, OR MODIFICATIONS OF EXISTING |
| | INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND |
| | ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE |
| | SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND |
| | APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER |
| | REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE |
| | FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR |
| | RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN |
| | INTO CONSIDERATION. |
| | SHOP DRAWING REVIEW AND APPROVAL BY THE DESIGNER OF |
| | RECORD BEFORE BEING SUBMITTED TO THE BUILDING |
| | DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT IS |
| | RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT |
| | DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 2) DEFERRED SUBMITTAL 107.3.4.2. SHEET S1 & S2 DRAWINGS |
| | BY GE HEALTHCARE. SHOW THE USE OF UNISTRUT SUPPORT AND |
| | EQUIPMENT TO BE HUNG FROM THE CEILING. SUBMIT SHOP |
| | DRAWINGS TO THE DESIGNER OF RECORD SHOWING THE |
| | ALLOWABLE AMOUNT OF LBS. TO BE HUNG FROM THE ASSEMBLY. |
| | SHOW THE ATTACHMENT TO THE STRUCTURAL STEEL OR THROUGH |
| | BOLT THROUGH CONCRETE FLOOR SHOULD BE FAVORED. DO NOT |
| | USE ANCHORS IN DIRECT TENSION. NOTE IF THE SHOP |
| | DRAWINGS WERE PREPARED BY AN ENGINEER, THEY WILL NEED |
| | TO BE SIGNED AND SEALED. FL ADMIN CODE 61G15-23.002 |
| | ENGINEERS. SINCE THE GE HEALTHCARE DRAWINGS ARE NOT |
| | SIGNED AND SEALED THE SHOP DRAWINGS BEING SUBMITTED |
| | WILL NEED TO BE REVIEWED AND APPROVED BY THE DESIGNER |
| | OF RECORD BEFORE BEING SUBMITTED TO THE BUILDING |
| | DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT IS |
| | RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT |
| | DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |