| 2017-03-10 10:35:49 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | RESIDENT INSPECTOR REQUIRED |
| | |
| | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| | |
| | 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE |
| | INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT |
| | REPORTS OF INSPECTORS OF RECOGNIZED INSPECTION |
| | SERVICES, PROVIDED THAT AFTER INVESTIGATION HE/SHE IS |
| | SATISFIED AS TO THEIR QUALIFICATIONS AND RELIABILITY. A |
| | CERTIFICATE CALLED FOR BY ANY PROVISION OF THE |
| | TECHNICAL CODES SHALL NOT BE BASED ON SUCH REPORTS |
| | UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY A |
| | RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE |
| | INCH |
| | 4. FOR PILE DRIVING |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. |
| | SUCH INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT, |
| | SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF |
| | COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE |
| | WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN |
| | ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION |
| | SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A |
| | CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION |
| | IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT |
| | ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS. |
| | |
| | 1. RESIDENT INSPECTOR AGREEMENT SHALL BE COMPLETED AND |
| | SUBMITTED IN TRIPLICATE. |
| | 2. PROVIDE RESUME OF RESIDENT INSPECTOR. |
| | 3. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468 |
| | INSPECTOR). |
| | 4. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY |
| | CONTRACTOR. |
| | |
| | FBC 3309 FIRE EXTINGUISHERS |
| | [F] 3309.1 WHERE REQUIRED. |
| | ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR |
| | DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE |
| | APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH |
| | SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD |
| | AS FOLLOWS: |
| | 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| | COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| | 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| | 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| | STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| | |
| | PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY LINES, |
| | CONSTRUCTION AREAS, STAGING AREAS, HOW THE OCCUPANTS OF |
| | THE BUILDING WILL BE SAFE GUARDED DURING THEIR ENTRY |
| | AND EXIT OF THE BUILDING. SHOW COMPLIANCE WITH 2014 FBC |
| | 3306.7 ? COVERED WALKWAYS, INCLUDING LIGHTING FOR THE |
| | EXIT DISCHARGE. 2014 FBC 3310.2 ? MAINTENANCE OF MEANS |
| | OF EGRESS. REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED |
| | AT ALL TIMES DURING CONSTRUCTION, DEMOLITION, |
| | REMODELING OR ALTERATIONS AND ADDITIONS TO ANY |
| | BUILDING. |
| | |
| | SECTION 3302 CONSTRUCTION SAFEGUARDS |
| | |
| | 3302.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE |
| | PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE |
| | MAINTAINED AT ALL TIMES DURING ALTERATIONS, REPAIRS OR |
| | ADDITIONS TO ANY BUILDING OR STRUCTURE. |
| | |
| | NOTICE ONLY: PLEASE CALL THE CITY OF WEST PALM BEACH?S |
| | AUTOMATED TELEPHONE INSPECTION LINE @ (561) 805-6700 |
| | FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. WITHOUT THIS, THE PERMIT EXPIRES IN 6 |
| | MONTHS WHICH WILL RESULT IN ?ABANDONMENT OF JOB, NO |
| | INSPECTION ACTIVITY?. THE PERMIT WILL BECOME EXPIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | ALL RESIDENT INSPECTOR DOCUMENTS SHALL BE SUBMITTED IN |
| | TRIPLICATE |
| | |
| | |
| | |