| Notes |
| Date |
Text |
| 2017-03-07 11:15:18 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THE AS-BUILT PLANS DO NOT INDICATE WHAT OR WHERE THE | | | AS-BUILTS ARE. | | | | | | PER NFPA 1, 5TH EDITION | | | | | | | | | 1.7.11 PLANS AND SPECIFICATIONS. | | | | | | 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS. | | | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | | | | | | FUTURE SUBMITTALS SHALL INDICATE AS-BUILTS WITH CLOUDS | | | OR CALL-OUTS OR IT WILL BE DENIED. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|