Plan Review Notes
Plan Review Notes For Permit 17030052
Permit Number 17030052
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-03-07 11:15:18THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE AS-BUILT PLANS DO NOT INDICATE WHAT OR WHERE THE
 AS-BUILTS ARE.
  
 PER NFPA 1, 5TH EDITION
  
  
 1.7.11 PLANS AND SPECIFICATIONS.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
  
 FUTURE SUBMITTALS SHALL INDICATE AS-BUILTS WITH CLOUDS
 OR CALL-OUTS OR IT WILL BE DENIED.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  