| Plan Review Notes For Permit 17030014 |
| Permit Number |
17030014 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-05-11 15:59:01 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SOME OF THE INFORMATION ON THE PLANS THAT WERE | | | SUBMITTED IS ILLEGIBLE. FBC 107.2.1 | | | | | | 2) THE RETURN AIR FOR THE LIBRARY IS CONNECTED TO THE | | | AIR HANDLER THAT DOES NOT SUPPLY AIR TO THE ROOM. THE | | | SUPPLY AND RETURN AIR NEED TO BE FROM THE SAME SYSTEM. | | | FBCR-M1601 | | | | | | 3) THERE ARE SOME DISCREPANCIES BETWEEN THE EQUIPMENT | | | SIZING CALCULATIONS, THE PLANS AND ENERGY FORM | | | R405-2014. THE FORM R405-2014 HAS 17,000 BTU OF HEAT | | | FOR THE #2 SYSTEM AND THE ENERGY CALCULATIONS HAS | | | 25,500 BTU. THE PLANS SPECIFY 10 KW FOR THE HEAT ON | | | SYSTEM #2 AND THE ENERGY CALCULATIONS SPECIFY 7.5 KW. | | | THE MODEL NUMBERS FOR THE EQUIPMENT ON THE PLANS DO NOT | | | MATCH THE ONES LISTED ON THE ENERGY CALCULATIONS. FBC | | | ENERGY CONSERVATION R-403.6 | | | | | | | | | | | | |
|