| 2017-04-18 16:21:50 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE SURVEY HAS THE STREET NAME FOR THIS PROJECT AS |
| | BAY POINTE LANE. THE PROPERTY APPRAISER AND CITY |
| | RECORDS INDICATE THAT THE STREET NAME IS HORIZON DRIVE. |
| | PLEASE REVISE THE SURVEY TO REFLECT THE STREET NAME AS |
| | HORIZON DRIVE. FBC 107.2.1 |
| | |
| | 2) UPDATE SHEETS A001 AND A801 TO REFERENCE THE 2014 |
| | FBC - RESIDENTIAL AND THE 2011 EDITIONS OF ACI 318, |
| | 315, 530, ASCE 5 AND TMS 402. FBC-R CHAPTER 46 |
| | |
| | 3) ON SHEET A001 UPDATE THE RESIDENTIAL POOL SAFETY ACT |
| | TO CHAPTER 45 OF THE 2014 FBC RESIDENTIAL AND DOOR & |
| | WINDOW REQUIREMENTS TO R4501.17 |
| | |
| | 4) ON SHEET A001 UPDATE THE TERMITE PROTECTION NOTE TO |
| | SECTION FBC-R 318 OF THE 2014 FBC. |
| | |
| | 5) ON SHEET S5 UPDATE THE REFERENCED MASONRY STANDARDS |
| | FROM THE 2008 TO THE 2011 EDITIONS. FBC-R CHAPTER 46 |
| | |
| | 6) THE WIND EXPOSURE CATEGORY IS SPECIFIED AS "C" ON |
| | SHEET A001 AND AS "D" ON SHEET S5. PLEASE REVISE PLANS |
| | TO BE CONSISTENT WITH REGARD TO THE EXPOSURE CATEGORY. |
| | FBC-R301.2.1.4 |
| | |
| | 7) PLEASE CLARIFY THE COMPONENT AND CLADDING DESIGN |
| | PRESSURES ON SHEET S5. THEY ARE +35.14, -38.54 PSF FOR |
| | WALL ZONE 4 AND +35.14, -43.83 PSF FOR WALL ZONE 5. THE |
| | EFFECTIVE WIND AREA IS NOT SPECIFIED. ASSUMING WORST |
| | CASE EFFECTIVE WIND AREA OF 10 SQFT., THESE PRESSURES |
| | ARE LOW FOR A STRUCTURE WITH A 20' MEAN ROOF HEIGHT |
| | LOCATED IN EXPOSURE D AND A 170 MPH VULT WIND SPEED. |
| | FBC-R301.2.1 |
| | |
| | 8) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. |
| | |
| | 9) THE PRODUCT APPROVAL INSTALLATION DRAWINGS THAT WERE |
| | SUBMITTED ARE TOO SMALL TO BE CLEARLY LEGIBLE. IT |
| | APPEARS THAT THEY SHOULD HAVE BEEN PRINTED IN LANDSCAPE |
| | ORIENTATION RATHER THAN PORTRAIT. PLEASE SUBMIT LARGER |
| | DRAWINGS. FBC 107.2.1 |
| | |
| | 10) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS |
| | WITH THE OUTDOOR BBQ'S LISTING INFORMATION AND |
| | INSTALLATION INSTRUCTIONS. IF A HOOD IS REQUIRED SUBMIT |
| | IT'S SPECIFICATIONS. FBC 107.2.1 |
| | |
| | 11) SPECIFY ON THE PLANS THE MATERIAL THAT WILL BE |
| | INSTALLED ON THE CEILING OF THE OUTDOOR LIVING AREA. |
| | FBC 107.2.1 |
| | |
| | 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |