| 2017-03-14 14:01:12 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17030013 | | | 3/14/17 | | | | | | 1) THE NEW DRESSING ROOM REQUIRES AN EXHAUST SYSTEM | | | WITH AN AIRFLOW RATE OF .25 CFM'S PER SQ FT.- SEE TABLE | | | 403.3. REVISE THE PLANS ACCORDINGLY | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|