| Plan Review Notes For Permit 17030007 |
| Permit Number |
17030007 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-07 17:52:34 | PLAN DENIED | | | 1) NEED DUCT SIZE ON 2ND FLOOR RETURN AIR DUCT 107 FBC | | | 2014 | | | 2) SHOW DRYER EXHAUST ON PLAN. PER SECTION M1502.3 FBC | | | 2014 | | | 3) PROVIDE TOTAL CFM FOR EACH UNIT ON PLANS. PER 107 | | | FBC | | | 4) PROVIDE MORE INFORMATION ON RETURN AIR PLENUM'S | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|