| Plan Review Notes For Permit 17030007 |
| Permit Number |
17030007 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-21 08:58:13 | INITIAL PLAN REVIEW ELECTRICAL 3/20/2017 | | | | | | 2814 N FLAGLER DR | | | PERMIT 17030007 | | | | | | | | | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | | | | COMMENTS: | | | | | | 1) PAGE A-6 SEPARATE STRUCTURE SHALL COMPLY WITH | | | 225.30, 225.31, 225.32, E3607.3 FBC RESIDENTIAL | | | 2) PAGE E-1 GENERAL OUTLET SPACING TO MEET E-3901.2, | | | E3901.2.1 FBC RESIDENTIAL | | | 3) GARAGE SHOWS NO OUTLETS E3901.9 FBC RESIDENTIAL | | | 4) LOAD NOT SHOWN FOR ELEVATOR | | | 5) DRYER LOAD IS 5000W MINIMUM | | | 6) NO CIRCUITS SHOWN FOR WASHER AND DRYER | | | 7) RISER DIAGRAM SHOS ONLY ONE PANEL | | | 8) OUTLETS IN THE OPEN AREA ON GROUND FLOOR SHALL BE | | | GFCI PROTECTED | | | 9) A SEPARATE PLAN AND PERMIT WILL BE REQUIRED FOR LV | | | SYSTEMS IF NOT SHOWN ON PLANS. | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | BN1165, BU1753, PX163 | | | 561-805-6713 | | | | | | | | | |
|