2017-03-06 19:00:52TRUSS DRAWING SUBMITTAL
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TRUSS ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 IS REQUIRED ON THE TRUSS DOCUMENTS. COPIES OR OTHER
 FACSIMILES ARE NOT ACCEPTABLE. FAC 61G15-23.001
  
 2) THE FLAT ROOF OF THE NEW TWO STORY GARAGE AND GUEST
 HOUSE IS DESIGNED TO BE USED AS A DECK AREA. THEREFORE,
 THE UFT1 ROOF TRUSSES ARE REQUIRED TO HAVE A TOP CORD
 LIVE LOAD OF 40 PSF AND A 20 PSF TOP CORD DEAD LOAD.
 THE BOTTOM CORD HAS A 10 PSF DEAD LOAD WHICH MAKES THE
 TOTAL LOAD 70 PSF. THE DESIGNER OF RECORD FOR THE
 STRUCTURE HAS NOTED THE REQUIRED CHANGES ON THE TRUSS
 DOCUMENTS. PLEASE MAKE THE CORRECTIONS AND RESUBMIT THE
 DOCUMENTS.
  
 3) THE EXPOSURE CATEGORY FOR THIS STRUCTURE IS "D". THE
 TRUSS LAYOUT DRAWING HAS THE BUILDING EXPOSURE AS "C".
 PLEASE CORRECT. FBC-R 301.2.1.4.3
  