| 2017-03-06 19:00:52 | TRUSS DRAWING SUBMITTAL | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE TRUSS ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | IS REQUIRED ON THE TRUSS DOCUMENTS. COPIES OR OTHER | | | FACSIMILES ARE NOT ACCEPTABLE. FAC 61G15-23.001 | | | | | | 2) THE FLAT ROOF OF THE NEW TWO STORY GARAGE AND GUEST | | | HOUSE IS DESIGNED TO BE USED AS A DECK AREA. THEREFORE, | | | THE UFT1 ROOF TRUSSES ARE REQUIRED TO HAVE A TOP CORD | | | LIVE LOAD OF 40 PSF AND A 20 PSF TOP CORD DEAD LOAD. | | | THE BOTTOM CORD HAS A 10 PSF DEAD LOAD WHICH MAKES THE | | | TOTAL LOAD 70 PSF. THE DESIGNER OF RECORD FOR THE | | | STRUCTURE HAS NOTED THE REQUIRED CHANGES ON THE TRUSS | | | DOCUMENTS. PLEASE MAKE THE CORRECTIONS AND RESUBMIT THE | | | DOCUMENTS. | | | | | | 3) THE EXPOSURE CATEGORY FOR THIS STRUCTURE IS "D". THE | | | TRUSS LAYOUT DRAWING HAS THE BUILDING EXPOSURE AS "C". | | | PLEASE CORRECT. FBC-R 301.2.1.4.3 | | | |
|