| 2017-03-01 07:26:36 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17021191 |
| | ADD: 5211 N. MILITARY TRAIL NORTH OBSERVATION TOWER |
| | CONT: THERMA SEAL ROOFING SYSTEMS, LLC |
| | TEL: 561-223-2096 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. MARCH 01/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE FLORIDA APPROVAL 16758-R7 JOHN MANVILLE TPO ROOF |
| | COVERING APPENDIX A INSTALLATION DETAILS THE BOTTOM |
| | RIGHT FASTENER PATTERN IS CIRCLED WITH THE NOTATION SEE |
| | ENGINEERING FOR CORNERS AND PERIMETER ZONES. PLEASE |
| | NOTE THERE IS NO ENGINEERING SUBMITTED WITHIN THIS |
| | PERMIT PACKAGE. SEE LIMITATION # 7 ENHANCED FASTENING |
| | IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES |
| | SHALL BE INCREASED FOR BOTH INSULATION & OR THE BASE |
| | SHEET AS CALCULATED IN COMPLIANCE WITH ROOFING |
| | APPLICATION STANDARDS RAS 117. CALCULATION PREPARED, |
| | SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL |
| | ENGINEER OR REGISTERED ARCHITECT. |