| Plan Review Notes For Permit 17021172 |
| Permit Number |
17021172 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-09 11:38:51 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A REVISED LOAD CALCULATION REFLECTING | | | NEW 80AMP BREAKER FROM EXISTING PANEL. FBC 107.3.5 | | | 2. ADDRESS ZONING COMMENTS FOR AN ELECTRICAL APPROVAL. | | | 3. PROVIDE A GENERAL NOTE TO PLAND TO COMPLY WITH FBC | | | RES 4302.5 OVERHEAD CONDUCTOR CLEARANCES. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|