2017-03-24 10:04:4103/24/17 TALKED TO TONY (A/C CONTRACTOR).
 NEED THE EQUIPMENT SIZING CALCULATIONS FOR THE REVISED
 EQUIPMENT AND THE RETURN AIR GRILL NEEDS TO BE AWAY
 FROM THE KITCHEN AREA.
  
  
  
  
 RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- SIZE OF EQUIPMENT SHOWN ON SHEET M101 WAS CHANGED.
 PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEC.
 M1401.3 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 2- RETURN AIR GRILL CAN NOT BE LOCATED IN THE KITCHEN.
 SEC. M1602.2(4) FBC-RESIDENTIAL. REVISE PLAN ON SHEET
 M101.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  