| Plan Review Notes For Permit 17021171 |
| Permit Number |
17021171 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-10 18:37:25 | RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- SIZE OF EQUIPMENT SHOWN ON SHEET M101 WAS CHANGED. | | | PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEC. | | | M1401.3 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | 2- RETURN AIR GRILL CAN NOT BE LOCATED IN THE KITCHEN. | | | SEC. M1602.2(4) FBC-RESIDENTIAL. REVISE PLAN ON SHEET | | | M101. | | | | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD | | | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS | | | FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|