| 2017-03-07 17:44:55 | 2210 NORTH AUSTRALIAN AVENUE | | | PERMIT 17021168 | | | FIRE DEPT PLAN REVIEW COMMENTS | | | | | | *****PROVISO - SUBMIT REVISION***** | | | | | | FIRST FLOOR RESIDENTIAL IS NOT DIVIDED INTO TWO SMOKE | | | COMPARTMENTS WITH SEPARATE FLOW SWITCHES. | | | | | | ARE EXISTING SPRINKLERS PROTECTING THE ELEVATOR PITS? | | | | | | NO SPRINKLERS PROTECTING SMALL CLOSESTS IN NEW | | | RESIDENTIAL BOARD AND CARE OCCUPANCY. PER NFPA 13 | | | SECTION 8.15.8.2 CLOSETS AND PANTRIES. SPRINKLERS ARE | | | NOT REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND | | | PANTRIES WITHIN DWELLING UNITS IN HOTELS AND MOTELS | | | WHERE THE AREA OF THE SPACE DOES NOT EXCEED 24 SQUARE | | | FEET, THE LEAST DIMENSION DOES NOT EXCEED 3 FEET, AND | | | THE WALLS AND CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE | | | OR LIMITED-COMBUSTIBLE MATERIALS. | | | | | | |
|