2017-03-07 17:44:552210 NORTH AUSTRALIAN AVENUE
 PERMIT 17021168
 FIRE DEPT PLAN REVIEW COMMENTS
  
 *****PROVISO - SUBMIT REVISION*****
  
 FIRST FLOOR RESIDENTIAL IS NOT DIVIDED INTO TWO SMOKE
 COMPARTMENTS WITH SEPARATE FLOW SWITCHES.
  
 ARE EXISTING SPRINKLERS PROTECTING THE ELEVATOR PITS?
  
 NO SPRINKLERS PROTECTING SMALL CLOSESTS IN NEW
 RESIDENTIAL BOARD AND CARE OCCUPANCY. PER NFPA 13
 SECTION 8.15.8.2 CLOSETS AND PANTRIES. SPRINKLERS ARE
 NOT REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND
 PANTRIES WITHIN DWELLING UNITS IN HOTELS AND MOTELS
 WHERE THE AREA OF THE SPACE DOES NOT EXCEED 24 SQUARE
 FEET, THE LEAST DIMENSION DOES NOT EXCEED 3 FEET, AND
 THE WALLS AND CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE MATERIALS.
  
  