| 2017-03-18 04:49:32 | 1) SHT. C-2 - ALL THE DRAIN LINES ON THE DRAWING ARE | | | LABELED AS "SANITARY" THOUGH THERE ARE GREASE WASTE | | | LINES ALSO.IDENTIFY THE GREASE WASTE LINES AS SUCH AND | | | CORRELATE THE GREASE WASTE LINES WITH THOSE SHOWN ON | | | DRAWING P-1.0.WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHT. C-2 - NOTES THE GREASE WASTE LINES AS FUTURE. | | | THERE ARE NO GREASE INTERCEPTORS INSTALLED ON ANY OF | | | THESE LINES. CLARIFY. COMPLY WITH 2014 FBC SEC. 1003.2. | | | 3) A CLEANOUT SHALL BE INSTALLED NOT MORE THAN 100 FEET | | | APART ON BUILDING SEWERS MEASURED FROM THE UPSTREAM | | | ENTRANCE OF THE CLEANOUT PER 2014 FBC-PLUMBING | | | SEC.708.3.2. | | | 4) A CLEANOUT BROUGHT TO GRADE SHALL ALSO BE LOCATED AT | | | THE PROPERTY LINE CONNECTION TO THE CITY LATERAL (WPB | | | UTILITIES REQUIREMENT). | | | 5) SUBMIT A STORMWATER RISER FOR REVIEW. WPB AMEND. TO | | | FBC SEC. 107.3.5.1.3. | | | 6) SHT. A-4.0 - INDICATE THE SLOPE OF THE HORIZONAL | | | STORM DRAIN PIPING PER 2014 FBC- PLUMBING TABLE 1106.3. | | | 7) SHOW THE GREASE WASTE LINES ON SHT. P-2.0. | | | 8) SEPARATE PERMITS WILL BE REQUIRED FOR THE BACKFLOW | | | DEVICES. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|