Plan Review Notes
Plan Review Notes For Permit 17021163
Permit Number 17021163
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-09 09:04:22INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE
 SYSTEMS. A NOTE WILL SUFFICE.
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 3. PLEASE SHOW THE SIZE OF WIRE-WAY. FBC 107.3.5
 4. LABEL MAINS 1OF2 2OF 2 ETC. PER NEC 230.2E
 5. PROVIDE A GENERAL NOTE TO INDICATE NEC 300.5 BURIAL
 DEPTH REQUIREMENTS.
 6. SHOW LIFE SAFETY EXIT LIGHTS AND EMERGENCY FIXTURES
 WITHIN SHELL AS SHOWN ON SHEET LSP1.0. PROVIDE LOADS ON
 HOUSE PANEL IF THAT IS WHERE THEY ORIGINATE FROM. SHOW
 ON PANEL SCHEDULE
 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  