| 2017-03-09 09:04:22 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL | | | SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE | | | SYSTEMS. A NOTE WILL SUFFICE. | | | 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC | | | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE | | | VERBIAGE IN CODE. | | | 3. PLEASE SHOW THE SIZE OF WIRE-WAY. FBC 107.3.5 | | | 4. LABEL MAINS 1OF2 2OF 2 ETC. PER NEC 230.2E | | | 5. PROVIDE A GENERAL NOTE TO INDICATE NEC 300.5 BURIAL | | | DEPTH REQUIREMENTS. | | | 6. SHOW LIFE SAFETY EXIT LIGHTS AND EMERGENCY FIXTURES | | | WITHIN SHELL AS SHOWN ON SHEET LSP1.0. PROVIDE LOADS ON | | | HOUSE PANEL IF THAT IS WHERE THEY ORIGINATE FROM. SHOW | | | ON PANEL SCHEDULE | | | 7. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|