| 2017-02-28 12:56:36 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17021161 |
| | 2/28/17 |
| | |
| | 1) PROVIDE COMPLETE AC EQUIPMENT SCHEDULES FOR SYSTEMS |
| | 1 & 2. |
| | |
| | 2) LABEL SYSTEM THE LOCATION OF SYSTEM #2 ON THE PLANS. |
| | |
| | 3) PROVIDE AN AC LAYOUT PLAN FOR THE SECOND FLOOR. |
| | |
| | 4) PROVIDE A RETURN GRILL FOR THE AC SYSTEM IN THE |
| | BEDROOM 1 CLOSET. |
| | |
| | 5) THE SUBMITTED AC CALCULATIONS APPEAR TO BE FOR THE |
| | FIRST FLOOR ONLY. PLEASE PROVIDE CALCULATIONS FOR THE |
| | SECOND FLOOR- SECTION R403.6.1 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | 6) FULL COMPLIANCE WITH THE FBC-14 ENERGY CONSERVATION |
| | CODE IS REQUIRED PER SECTION R101.4.5. PLEASE SUBMIT |
| | EITHER FORM R402 FOR PRESCRIPTIVE COMPLIANCE OR FORM |
| | R405 USING APPROVED SOFTWARE SUCH AS ENERGYGAUGE FOR |
| | PERFORMANCE BASED COMPLIANCE. |
| | |
| | 7) PROVIDE A CONDENSATE DISPOSAL PLAN FOR EACH AIR |
| | HANDLER. |
| | |
| | 8) PROVIDE A DETAIL FOR INSTALLATION OF THE FIRE DAMPER |
| | AT THE DUCT PENETRATIONS OF THE FLOOR/CEILING |
| | ASSEMBLIES. PLEASE INCLUDE A DETAIL OF THE ACTUAL |
| | FLOOR/CEILING ASSEMBLY INCLUDING THE HOURLY |
| | FIRE-RATING. |
| | |
| | 9) AN APPLICATION FOR BUSINESS LICENSING MUST BE |
| | SUBMITTED. PLEASE CONTACT RACHELSKLAREW- LICENSE & |
| | PERMIT SPECIALIST SUPERVISOR- 561-805-6688. |
| | |
| | 10) PLEASE NOTE THAT AN INCREASE IN VALUE WILL BE |
| | REQUIRED FOR THE ENTIRE SCOPE OF WORK FOR THE PROJECT- |
| | SEE SECTION 109.3 WPB AMENDMENTS TO THE FBC. |
| | |