| Plan Review Notes For Permit 17021129 |
| Permit Number |
17021129 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-10 10:20:36 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR WATER | | | HEATER AND DRYER. PER THE FBC-2014 FUEL GAS CODE SEC. | | | 304 | | | | | | 2.THE FIRST SECTION OF CSST UPSTREAM OF THE DRYER | | | SHOULD BE EHD OF 37 OR 11/4 CSST . PER FBC FUEL GAS | | | TABLE 402.4(15) | | | | | | 3. THE SECOND SECTION OF CSST BETWEEN DRYER AND COOK | | | TOP SHOULD BE EHD OF 31 OR 1" CSST . PER FBC FUEL GAS | | | TABLE 402.4(15) | | | | | | 4.THE NOTE ON THE PLAN UNDER NAT. GAS @ 12-14" WC | | | STATES TOTAL BTU 568M THE RISER AND APPLIANCE SCHEDULE | | | SHOWS TOTAL BTU LOAD AT 168M PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 5. PLEASE PROVIDE SIZING TABLES USED TO SIZE SYSTEM. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|