2017-03-10 10:20:361ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR WATER
 HEATER AND DRYER. PER THE FBC-2014 FUEL GAS CODE SEC.
 304
  
 2.THE FIRST SECTION OF CSST UPSTREAM OF THE DRYER
 SHOULD BE EHD OF 37 OR 11/4 CSST . PER FBC FUEL GAS
 TABLE 402.4(15)
  
 3. THE SECOND SECTION OF CSST BETWEEN DRYER AND COOK
 TOP SHOULD BE EHD OF 31 OR 1" CSST . PER FBC FUEL GAS
 TABLE 402.4(15)
  
 4.THE NOTE ON THE PLAN UNDER NAT. GAS @ 12-14" WC
 STATES TOTAL BTU 568M THE RISER AND APPLIANCE SCHEDULE
 SHOWS TOTAL BTU LOAD AT 168M PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 5. PLEASE PROVIDE SIZING TABLES USED TO SIZE SYSTEM.
 PER WPB AMEND TO FBC 107.2.1
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  