| 2017-03-07 11:45:04 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- GARAGE DOOR STRUCTURAL BUCK: PROVIDE COMPLETE DETAIL | | | AND SPECIFICATIONS FOR THE ATTACHMENT OF THE STRUCTURAL | | | BUCK TO THE SUPPORTING STRUCTURE. SPECIFY BUCK SIZE, | | | FASTENER TYPE, SIZE AND SPACING. DETAIL #11 ON SHEET | | | 12ABCD DOESN'T PROVIDE THIS INFORMATION. | | | 2- ARROW ORIENTATION SHOWN ON SHEET 2 OF 2 OF SURVEY | | | SUBMITED IS INCORRECT. REVISE AS REQUIRED. | | | 3- TRUSS PACKAGE SUBMITTED: THERE IS NO NEED TO SUBMIT | | | TRUSS PACKAGE FOR SINGLE FAMILY RESIDENCES (R3). THE | | | TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED IN | | | WRITING BY THE ARCHITECT OF RECORD. THEN, DELIVER THE | | | TRUSS PACKAGE TO THE BUILDING INSPECTOR AT TIME OF | | | FRAMING INSPECTION. |
|