| Plan Review Notes For Permit 17021107 |
| Permit Number |
17021107 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-08 12:32:08 | 1) SUBMIT TWO COPIES OF THE COMPLETE FSEC CERTIFICATION | | | FOR THE SOLAR COLLECTOR AND ALSO FOR THE THERMAL SYSTEM | | | FROM THE FSEC WEBSITE. THERE ARE 3 PAGES FOR EACH | | | CERRTIFICATION. REFER TO FSEC CERTIFICATION # 00472N & | | | #S00171A. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHT. 1 OF 1 OF THE DRAWING SIGNED & SEALED BY | | | J.TORRES - SOLENE TILTED MOUNT NOTES- NOTE #6 REFERS TO | | | THE SOLENE INSTALLATION MANUAL FOR THE PLUMBING & SOLAR | | | SPECS. SUBMIT TWO COPIES OF THIS MANUAL FOR REVIEW. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 3) SHOW THE SIZE OF THE EXPANSION TANK ON THE DIAGRAM. | | | 4) INDICATE IF THE SOLAR SYSTEM WILL BE SUBJECTED TO A | | | VACUUM AND IF SO COMPLY WITH 2014 FBC-MECHANICAL SEC. | | | 1402.5.2. | | | 5) 2014 FBC-ENERGY - SEC. R403.4.1 - CIRCULATING HOT | | | WATER SYSTEMS SHALL BE PROVIDED WITH AN AUTOMATIC OR | | | READILY ACCESSIBLE MANUAL SWITCH THAT CAN TURN OFF THE | | | HOT WATER CIRCULATING PUMP WHEN THE SYSTEM IS NOT IN | | | USE. | | | 6) INSULATION FOR THE HOT WATER PIPE SHALL COMPLY WITH | | | 2014 FBC-ENERGY SEC.R403.4.2. | | | 7) HEAT TRAPS ARE REQD. ON THE WATER HEATER. 2014 | | | FBC-ENERGY SEC.R403.4.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|