| Date |
Text |
| 2017-08-04 14:16:24 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17021104 |
| | ADD: 2905 45TH ST. |
| | CONT: SUPERIOR CONCRETE INC. / CBC1256722 |
| | TEL: 561-328-3575 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: FRI. AUGUST 4, 2017 |
| | ACTION: DENIED |
| | |
| | NOTICE: SAME PLAN AS 1ST REVIEW, NO CHANGES. |
| | 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1) 3RD REQUEST. SEMI-COMPLIED. SHEET SP1. THE DESIGNER |
| | OF RECORD HAS PROVIDED THE 1ST FLOOR SQUARE FOOTAGE |
| | (FOOT PRINT) 9390 AND OCCUPANT LOAD 1ST FLOOR ONLY OF |
| | 337. THE PLAN ALSO INDICATES A 2ND FLOOR AREA OF 1215 |
| | SQUARE FEET ENCLOSED AND MEZZANINE AREA OF 2776 SQ. FT. |
| | BUT HAS NOT PROVIDED THE OCCUPANT LOADS FOR THESE |
| | AREAS. IT IS CRITICAL TO HAVE A TOTAL OCCUPANT LOAD |
| | SINCE THIS IS A ASSEMBLY OCCUPANCY. |
| | CODE COMPLIANCE CANNOT BE ACHIEVED WITHOUT A TOTAL |
| | COUNT. |
| | 2014 FBC-B 1004.1.1 CUMULATIVE OCCUPANT LOADS. WHERE |
| | THE PATH OF EGRESS TRAVEL INCLUDES INTERVENING ROOMS, |
| | AREAS OR SPACES, CUMULATIVE OCCUPANT LOADS SHALL BE |
| | DETERMINED IN ACCORDANCE WITH THIS SECTION. |
| | |
| | 2014 FBC-B 1004.1.1.1 INTERVENING SPACES. WHERE |
| | OCCUPANTS EGRESS FROM ONE ROOM, AREA OR SPACE THROUGH |
| | ANOTHER, THE DESIGN OCCUPANT LOAD SHALL BE BASED ON THE |
| | CUMULATIVE OCCUPANT LOADS OF ALL ROOMS, AREAS OR SPACES |
| | TO THAT POINT ALONG THE PATH OF EGRESS TRAVEL. |
| | |
| | 2ND REQUEST. PLEASE NOTE SHEET SP-1 NOTES THE CODE DATA |
| | WHAT IS MISSING FROM THIS PLAN IS THE OCCUPANT LOAD FOR |
| | THE 1ST AND 2ND FLOORS. THE W. P. B. PERMIT: 13120617 |
| | LIST THE TOTAL OCCUPANT LOAD FOR THE 1ST AND 2ND FLOORS |
| | AS 489 OCCUPANTS. PLEASE UPDATE THE PLANS. 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING. |
| | (7) OCCUPANT LOAD. |
| | |
| | 2-5) COMPLIED. |
| | |
| | 6) SEMI-COMPLIED. THE PLANS NOW SHOW THE DOOR UNDER THE |
| | NEW EXTERIOR STAIR WITH A 45 MINUTE FIRE RATING BUT |
| | THERE IS NO RATING ON THE NEW 2ND FLOOR EXIT. I WAS |
| | HOPING THE DESIGNER OF RECORD WAS GOING TO SHOW BOTH |
| | DOOR BEING FIRE RATED. IN THE 2014 FBC-B SECTION 1026.6 |
| | EXTERIOR STAIRWAY AND RAMP PROTECTION. EXTERIOR EXIT |
| | STAIRWAYS AND RAMPS SHALL BE SEPARATED FROM THE |
| | INTERIOR OF THE BUILDING AS REQUIRED IN SECTION 1022.2. |
| | 1022.2 CONSTRUCTION. ENCLOSURES FOR INTERIOR EXIT |
| | STAIRWAYS AND RAMPS SHALL BE CONSTRUCTED AS FIRE |
| | BARRIERS IN ACCORDANCE WITH SECTION 707 OR HORIZONTAL |
| | ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 711, |
| | OR BOTH. INTERIOR EXIT STAIRWAY AND RAMP ENCLOSURES |
| | SHALL HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 |
| | HOURS WHERE CONNECTING FOUR STORIES OR MORE AND NOT |
| | LESS THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR |
| | STORIES. |
| | THE 2012 ICC COMMENTARY FIGURE 1026.6(1) SHOWS ALL |
| | DOORS THAT LEAD FROM THE INTERIOR TO BE FIRE RATED. |
| | BUILDINGS LESS THAN 4 STORIES, THE DOORS ONLY REQUIRE A |
| | 45 MINUTE RATING. |
| | |
| | 2ND REQUEST, PLAN NOT CHANGED. SHEET A-1.1 DETAIL # 1 |
| | SHOWS AN EXISTING DOOR UNDER THE MID-LANDING. THIS DOOR |
| | WILL NEED TO BE A ONE-HOUR FIRE RATED DOOR. SEE FBC-B |
| | 1026.6. |
| | |
| | 7) 3RD REQUEST. NO RESPONSE FROM THE ARCHITECT OF |
| | RECORD, ENGINEER OF RECORD HAD A NARRATIVE. 2ND |
| | REQUEST, PLAN NOT CHANGED. SHEET A-1.0 SHOWS THE 1ST |
| | FLOOR EXIT DOOR AND THE NEW PROPOSED EXTERIOR STAIR |
| | ABOVE. THE NEW STAIR BLOCKS THE EGRESS PATH TO THE |
| | PUBLIC WAY PLEASE PROVIDE DETAILS COMPLYING WITH |
| | 1027.4.1 WIDTH. A SECOND CONCERN IS COMPLIANCE WITH |
| | FBC-B 1027.4.2 EGRESS COURTS THAT ARE WITHIN 10 FEET OF |
| | THE PROPERTY LINE WHICH IN THIS AREA THE EGRESS PATH |
| | WOULD BE! |
| | |
| | 8)3RD RESPONSE, THE ENGINEER OF RECORD INDICATED THAT |
| | IT IS UP TO THE CONTRACTOR TO SUBMIT THE SOILS REPORT. |
| | 2ND REQUEST, PLAN NOT CHANGED. THE SHEET S-1 UNDER THE |
| | FOUNDATION NOTE # 1 DOES REQUIRE A SOILS INVESTIGATION |
| | BY AN APPROVED TESTING LAB, THIS AREA IS IN A |
| | QUESTIONABLE SOILS ZONE. FBC-B 1803.5.2. |
| | |
| | 9-10) COMPLIED. |
| | |
| | 11)PROVISO: WELDED OR BOLTED CONNECTIONS. THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS. |
| | 2014 FBC-B 2204.1 WELDING |
| | 201404.4.2 BOLTING. |
| | |
| | 12) COMPLIED. QUALIFIER FOR THE CONTRACTOR HAS SIGNED |
| | AND NOTARIZED THE PERMIT APPLICATION. 105.1 PERMIT |
| | REQUIRED. |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |