| 2017-07-12 07:15:25 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17021104 |
| | ADD: 2905 45TH ST. |
| | CONT: SUPERIOR CONCRETE INC. / CBC1256722 |
| | TEL: 561-328-3575 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. JULY12/ 2017 |
| | ACTION: DENIED |
| | |
| | NOTICE: SAME PLAN AS 1ST REVIEW, NO CHANGES. |
| | 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1) 2ND REQUEST, PLAN NOT CHANGED. PLEASE NOTE SHEET |
| | SP-1 NOTES THE CODE DATA WHAT IS MISSING FROM THIS PLAN |
| | IS THE OCCUPANT LOAD FOR THE 1ST AND 2ND FLOORS. THE W. |
| | P. B. PERMIT: 13120617 LIST THE TOTAL OCCUPANT LOAD FOR |
| | THE 1ST AND 2ND FLOORS AS 489 OCCUPANTS. PLEASE UPDATE |
| | THE PLANS. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING. |
| | (7) OCCUPANT LOAD. |
| | |
| | 2) 2ND REQUEST, PLAN NOT CHANGED. PLEASE NOTE THE SHEET |
| | S-1.0 UNDER THE WIND DESIGN CRITERIA LIST THE BUILDING |
| | RISK CATEGORY II AND IN A 170 VULT WIND ZONE. PLEASE |
| | REVIEW THE 2014 FBC-B TABLE 1604.5 RISK CATEGORY OF |
| | BUILDINGS, UNDER THE RISK CATEGORY III BUILDINGS WHOSE |
| | PRIMARY OCCUPANCY IS PUBLIC ASSEMBLY WITH AN OCCUPANT |
| | LOAD GREATER THAN 300. PLEASE UPDATE THE VULT WIND |
| | DESIGN TO 180 MPH, 3 SECOND GUST SEE FIGURE 1609B |
| | ULTIMATE DESIGN SPEEDS FOR RICK CATEGORY III BUILDINGS. |
| | |
| | 3) 2ND REQUEST, PLAN NOT CHANGED. PLEASE PROVIDE THE |
| | WIND DESIGN PRESSURES FOR THE 180 VULT WIND SPEED IN |
| | VASD SINCE THE PRODUCT APPROVALS ARE IN VASD. PLEASE |
| | ALSO PROVIDE THE MEAN ROOF HEIGHT OF THE BUILDING FOR |
| | COMPLIANCE WITH FBC-B TABLE 1609.7(2) ADJUSTMENT |
| | FACTORS FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF |
| | HEIGHT FOR THE BUILDING. |
| | |
| | 4) 2ND REQUEST, PLANS NOT CHANGED. NEITHER THE |
| | ARCHITECTURAL NOR STRUCTURAL SHEETS PROVIDE THE LIVE |
| | LOAD VALUE THAT THE STEEL STAIRS SHOULD BE DESIGNED |
| | TOO? FBC-B TABLE 1607.1 (30) 100 (PSF/ UNIFORM). THE |
| | PLANS INDICATE THE STAIR ENGINEERING ARE TO BE |
| | COMPLETED BY OTHERS, ONCE THE DESIGN LOADS ARE KNOWN |
| | THE STEEL STAIR SHOP DRAWINGS CAN BE A DEFERRED |
| | SUBMITTAL. . FL 61G-15-30.006 (3) THE DELEGATED |
| | ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| | DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 5) COMPLIED. |
| | |
| | 6)2ND REQUEST, PLAN NOT CHANGED. SHEET A-1.1 DETAIL # 1 |
| | SHOWS AN EXISTING DOOR UNDER THE MID-LANDING. THIS DOOR |
| | WILL NEED TO BE A ONE-HOUR FIRE RATED DOOR. SEE FBC-B |
| | 1026.6. |
| | |
| | 7) 2ND REQUEST, PLAN NOT CHANGED. SHEET A-1.0 SHOWS THE |
| | 1ST FLOOR EXIT DOOR AND THE NEW PROPOSED EXTERIOR STAIR |
| | ABOVE. THE NEW STAIR BLOCKS THE EGRESS PATH TO THE |
| | PUBLIC WAY PLEASE PROVIDE DETAILS COMPLYING WITH |
| | 1027.4.1 WIDTH. A SECOND CONCERN IS COMPLIANCE WITH |
| | FBC-B 1027.4.2 EGRESS COURTS THAT ARE WITHIN 10 FEET OF |
| | THE PROPERTY LINE WHICH IN THIS AREA THE EGRESS PATH |
| | WOULD BE! |
| | |
| | 8) 2ND REQUEST, PLAN NOT CHANGED. THE SHEET S-1 UNDER |
| | THE FOUNDATION NOTE # 1 DOES REQUIRE A SOILS |
| | INVESTIGATION BY AN APPROVED TESTING LAB, THIS AREA IS |
| | IN A QUESTIONABLE SOILS ZONE. FBC-B 1803.5.2. |
| | |
| | 9-10) COMPLIED. |
| | |
| | 11)PROVISO: WELDED OR BOLTED CONNECTIONS. THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS. |
| | 2014 FBC-B 2204.1 WELDING |
| | 201404.4.2 BOLTING. |
| | |
| | 12) COMPLIED. QUALIFIER FOR THE CONTRACTOR HAS SIGNED |
| | AND NOTARIZED THE PERMIT APPLICATION. 105.1 PERMIT |
| | REQUIRED. |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |