Plan Review Notes
Plan Review Notes For Permit 17021104
Permit Number 17021104
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-03-02 09:41:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1)
 SHEET A 1.1 - THE DOOR UNDER THE STAIR IS NOTED AS
 EXISTING; HOWEVER, PER NFPA 101, CHAPTER 7, MEANS OF
 EGRESS, THE DOOR ASSEMBLY SHALL HAVE MINIMUM 1 HOUR
 FIRE RATING.
  
 7.2.2.6.4 PROTECTION OF OPENINGS. ALL OPENINGS BELOW AN
 OUTSIDE STAIR SHALL BE PROTECTED WITH AN ASSEMBLY
 HAVING A MINIMUM ?- HOUR FIRE PROTECTION RATING AS
 FOLLOWS:
 (1) WHERE LOCATED IN AN ENCLOSED COURT (SEE 3.3.51.1),
 THE SMALLEST DIMENSION OF WHICH DOES NOT EXCEED
 ONE-THIRD ITS HEIGHT
 (2) WHERE LOCATED IN AN ALCOVE HAVING A WIDTH THAT DOES
 NOT EXCEED ONE-THIRD ITS HEIGHT AND A DEPTH THAT DOES
 NOT EXCEED ONE-FOURTH ITS HEIGHT
  
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 2)
 SHEET SP 1 - THERE IS NO OCCUPANCY LOAD INDICATED FOR
 THE 2ND FLOOR AREA THE STAIR SERVES.
  
 PLEASE REVIEW AND PROVIDE DETAILS TO ENSURE AND CONFIRM
 THAT THE DOOR AND STAIR DIMENSIOND MEET THE NFPA 101
 EGRESS CODE.
  
  
  
 3)
 SHEET A 1.1 - THERE IS INSUFFICIENT DETAIL INDICATED
 REGARDING THE GUARDRAIL.
  
 7.2.2.4.5 GUARD DETAILS. SEE 7.1.8 FOR GUARD
 REQUIREMENTS.
 7.2.2.4.5.1 THE HEIGHT OF GUARDS REQUIRED IN 7.1.8
 SHALL BE MEASURED VERTICALLY TO THE TOP OF THE GUARD
 FROM THE SURFACE ADJACENT THERETO.
 7.2.2.4.5.2 GUARDS SHALL BE NOT LESS THAN 42 IN. (1065
 MM) HIGH, EXCEPT AS PERMITTED BY ONE OF THE FOLLOWING:
 (1) EXISTING GUARDS WITHIN DWELLING UNITS SHALL BE
 PERMITTED TO BE NOT LESS THAN 36 IN. (915 MM) HIGH.
 (2) THE REQUIREMENT OF 7.2.2.4.5.2 SHALL NOT APPLY IN
 ASSEMBLY OCCUPANCIES WHERE OTHERWISE PROVIDED IN
 CHAPTERS 12 AND 13.
 (3)* EXISTING GUARDS ON EXISTING STAIRS SHALL BE
 PERMITTED TO BE NOT LESS THAN 30 IN. (760 MM) HIGH.
 7.2.2.4.5.3* OPEN GUARDS, OTHER THAN APPROVED EXISTING
 OPEN GUARDS, SHALL HAVE INTERMEDIATE RAILS OR AN
 ORNAMENTAL PATTERN SUCH THAT A SPHERE 4 IN. (100 MM) IN
 DIAMETER IS NOT ABLE TO PASS THROUGH ANY OPENING UP TO
 A HEIGHT OF 34 IN. (865 MM), AND THE FOLLOWING ALSO
 SHALL APPLY:
 (1) THE TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD,
 AND BOTTOM ELEMENT OF A GUARDRAIL AT THE OPEN SIDE OF A
 STAIR SHALL BE OF SUCH SIZE THAT A SPHERE 6 IN. (150
 MM) IN DIAMETER IS NOT ABLE TO PASS THROUGH THE
 TRIANGULAR OPENING.
 (2) IN DETENTION AND CORRECTIONAL OCCUPANCIES, IN
 INDUSTRIAL OCCUPANCIES, AND IN STORAGE OCCUPANCIES, THE
 CLEAR DISTANCE BETWEEN INTERMEDIATE RAILS, MEASURED AT
 RIGHT ANGLES TO THE RAILS, SHALL NOT EXCEED 21 IN. (535
 MM).
  
 PLEASE PROVIDE GREATER DETAIL INDICATING ALL DIMENSIONS
 MEETING THE REQUIRMENTS OF NFPA 101 MEANS OF EGRESS.
  
  
  
 4)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 5)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  