| Plan Review Notes For Permit 17021076 |
| Permit Number |
17021076 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-02-28 09:13:55 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PROFLEX 90 MSC UNDERLAYMENT WAS TESTED FOR AIR | | | BORNE AND STRUCTURAL SOUND TRANSMISSIONS WITH TILE ON | | | AN 8" CONCRETE SLAB WITH A SUSPENDED GYPSUM BOARD | | | CEILING. THIS IS NOT THE FLOOR CEILING ASSEMBLY FOR | | | YOUR PROPOSED INSTALLATION. SUBMIT TWO COPIES OF THE | | | PRODUCT TESTING FOR A 6" SLAB WITH NO SUSPENDED CEILING | | | WHICH HAS SOUND TRANSMISSION RATINGS (STC AND II2) OF | | | NOT LESS THAN 50. ALSO, SUBMIT TWO COPIES OF THE FLAME | | | SPREAD AND SMOKE DEVELOPED TEST REPORTS ON THE PRODUCT. | | | THE FLAME SPREAD INDEX MUST BE NO MORE THAN 25 AND | | | SMOKE DEVELOPED INDEX CAN BE NO MORE THAN 450. FBC | | | 1207.2, 1207.3 & 720.2 |
|