| Plan Review Notes For Permit 17021070 |
| Permit Number |
17021070 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-02 07:38:30 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17021070 | | | 3/2/17 | | | | | | 1) SHEET M-2: THE DIFFUSER TAGS AND CFMS ARE MISSING IN | | | THE BREAKROOM AND THE TECH ROOM. | | | | | | 2) M-2: THE ORIGINAL APPROVED PLAN INDICATES 1140 CFMS | | | OF SUPPLY AIR PROVIDED TO THE TECH ROOM WHICH WOULD | | | INDICATE THE TWO 10X10 TA GRILLES ARE UNDERSIZED- SEE | | | SECTION 601.5 (2) AND PROVIDE TRANSFER GRILLS SIZED AT | | | 50 SQ. INCHES PER 100 CFM OF SUPPLY AIR. | | | | | | 3) PLEASE BIND THE PLANS TOGETHER- SECTION 107.2.1 WPB | | | AMENDMENTS TO THE FBC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|