| Plan Review Notes For Permit 17021061 |
| Permit Number |
17021061 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-31 10:44:09 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR: | | | A) NEW ENTRY DOOR AS SHOWN ON PLANS. PROVIDE THE | | | FLORIDA PRODUCT APPROVAL COVER PAGE FOR DRAWINGS | | | SUBMITED. IF THERE IS NOT FLORIDA PRODUCT APPROVAL, | | | THEN DOOR MANUFACTURER MAY SUBMITT COMPLETE ORIGINAL | | | ENGINEERING PACKAGE FOR LOCAL PRODUCT APPROVAL BY | | | BUILDING OFFICIAL. | | | | | | B) NEW SINGLE HUNG WINDOWS AS SHOWN ON PLANS. | | | | | | C) HURRICANE SHUTTERS IF WINDOWS DON'T HAVE IMPACT | | | GLAZING. AND PROVIDE COMPLETE INSTALLATION SCHEDULE. | | | SEE CITY SAMPLE. | | | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 3- PRODUCT APPROVALS INFORMATION SHOWN ON SHEET S-1 AND | | | S-3 DON'T MATCH PRODUCT APPROVALS SUBMITTED. ENGINEER | | | OF RECORD TO REVISE AS REQUIRED TO MATCH.. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | 4- ENGINEER OF RECORD TO CLARIFY SCOPE OF WORK NOTE # 2 | | | ON SHEET D-1. THERE IS NOT BATHROOM #4. REVISE AS | | | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|