| Plan Review Notes For Permit 17021032 |
| Permit Number |
17021032 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-12 15:52:23 | PLAN DENIED | | | 1) AHU # 2 REFER TO SECTION M1602.2 PROHIBITED | | | SOURCES # 1 RETURN AIR IN KITCHEN MUST BE 10 FT. | | | FROM ANY APPLIANCE.2014 FRC | | | 2) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS | | | ON THE KITCHEN HOOD AT FIRST INSPECTION. | | | 3) AHU # 3 PROVIDE SIZE OF GRILL IN FOYER ON THE PLAN. | | | 4) SHOW LOCATION OF ALL 6 CONDENSERS ON THE PLAN | | | SECTION 107-FBC. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|