| Plan Review Notes For Permit 17021026 |
| Permit Number |
17021026 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-07 16:20:24 | 17021026 | | | | | | 1) RISER DIGRAM NEEDED 215.5 | | | | | | 2) LOAD CALCULATION FBC RESIDENTIA E 3602.2 | | | | | | 3) PANEL SCHEDULE(S) FBC RESIDENTIAL E 3706.2 | | | | | | 4) FIRST FLOOR SA SHOULD BE CO2 AND WITHIN 10' OF | | | BEDROOM DOOR R-315.1 | | | | | | 5) SAME AT TOP OF THE STAIRS R-315.1 | | | | | | 6) LIGHT FIXTURE LAMPS TO BE 75% HIGH EFFICINCY FBC EC | | | R 404.1 | | | | | | 7) NEED TO SHOW SERVICE LOCATION AND PANEL LOCATION | | | | | | 8) FRONT/REAR OUTLETS MISSING FBC RESIDENTIAL E3901.7 | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | WEST PALM BEACH, FL | | | |
|