| Date |
Text |
| 2017-05-09 04:53:04 | 1) AS A NOTE OF INFORMATION, A SEPARATE PERMIT WILL BE |
| | REQUIRED FOR THE NEW BACKFLOW PREVENTER LOCATED AT THE |
| | NEW WATER METER. THE DEVICE SHALL BE LEAD- FREE AND |
| | COMPLY WITH THE CITY OF WPB CROSS-CONNECTION CONTROL |
| | MANUAL AND MUST ALSO BE ON THE UNIVERSITY OF SOUTHERN |
| | CALIFORNIA'S (USC) LIST OF APPROVED DEVICES. TWO COPIES |
| | OF THE MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED |
| | AT THE TIME OF PERMIT APPLICATION. 2014 FBC-PLUMBING |
| | SEC.605.2.1. THE CITY OF WPB CROSS-CONNECTION MANUAL |
| | CAN BE VIEWED AT HTTP://WPB.ORG/UTILITIES/BACKFLOW. |
| | 2) SHT. A 8.02 - DETAIL #3 - THE SIDE WALL GRAB BAR |
| | NEXT TO THE WATER CLOSET SHALL BE LOCATED PER 2014 |
| | FBC-ACCESS.SEC. 604.5.1 & FIGURE 604.5.1. THE GRAB BAR |
| | SHALL EXTEND A MINIMUM OF 54 INCHES FROM THE REAR |
| | WALL.THE DETAIL SHOWS THE GRAB BAR 10 1/2 INCHES FROM |
| | THE REAR WALL WHICH WILL PRODUCE 52 1/2 INCHES FROM THE |
| | REAR WALL USING A 42 INCH BAR AND A MINIMUM OF 54 |
| | INCHES IS REQUIRED. 2ND REQUEST. |
| | 3) SHT. A 8.02 - DETAILS #3 & #4 - THE TOILET PAPER |
| | DISPENSER SHALL BE LOCATED 7 INCHES MINIMUM AND 9 |
| | INCHES MAXIMUM TO THE CENTER OF THE FIRST TOILET PAPER |
| | ROLL, NOT TO THE CENTER OF THE DOUBLE ROLL DISPENSER AS |
| | SHOWN ON THE PLANS.FBC-ACCESS SEC.604.7. 2ND REQUEST. |
| | 4) THE DETAIL OF THE HOT WATER RECIRCULATING SYSTEM ON |
| | DETAIL #1 ON SHT.P0.1 DOES NOT APPEAR TO COMPLY WITH |
| | 2014 FBC-PLUMBING SEC.607.2.2. I DO NOT SEE A HOT WATER |
| | RETURN LINE COMING FROM THE FIXTURES BACK TO THE WATER |
| | HEATERS. PLEASE REFER TO THE FOLLOWING TEXT FROM THE |
| | PLUMBING CODE: |
| | 607.2.2 RECIRCULATING PUMP. |
| | WHERE A THERMOSTATIC MIXING VALVE IS USED IN A SYSTEM |
| | WITH A HOT WATER RECIRCULATING PUMP, THE HOT WATER OR |
| | TEMPERED WATER RETURN LINE SHALL BE ROUTED TO THE COLD |
| | WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER |
| | INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE |
| | THERMOSTATIC MIXING VALVE. |
| | 5) THE DESIGN OF THE GREASE INTERCEPTOR SHALL COMPLY |
| | WITH THE CITY OF WEST PALM BEACH STANDARD DRAWING GS-7 |
| | FOR CONCRETE TANKS AND DRAWING GS-7.1 FOR |
| | HYDR-MECHANICAL TANKS. I HAVE INCLUDED COPIES OF THESE |
| | STANDARD DRAWINGS IN THE PERMIT APPLICATION SUBMITTAL |
| | PACKAGE FOR YOUR PERUSAL. AS A NOTE OF INFORMATION, THE |
| | INTERCEPTOR SHALL BE PERMITTED UNDER A SEPARATE PERMIT. |
| | ENSURE THE SIZE AND LOCATION OF THE FLOW THROUGH HOLE |
| | IN THE BAFFLE COMPLIES WITH THE CITY'S STANDARD |
| | DRAWING. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |