| Plan Review Notes For Permit 17021025 |
| Permit Number |
17021025 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-04-20 14:07:44 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. REGARDING THE ALTERNATING STAIRS, THE BUILDING | | | OFFICIAL HAS THE FOLLOWING REQUIREMENTS: | | | | | | THE LETTER DOES NOT INCLUDE A PROJECT NAME, ADDRESS, OR | | | PERMIT NUMBER. INCORPORATE THIS INFORMATION INTO THE | | | LETTER. | | | | | | THE LETTER STATES THAT ALL ACCESS IS FROM EXTERIOR. | | | REVISE THE PLAN (BOTH PERMIT DRAWINGS AND PLAN INCLUDED | | | IN THE LETTER) AT THE RAILING (WHERE IT STATES OPEN TO | | | BELOW) TO STATE THAT THERE WILL BE NO ACCESS FROM THE | | | STORAGE LOFT TO THE INTERIOR. | | | | | | |
|