| 2017-03-01 09:58:39 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17021025 |
| | 3/1/17 |
| | |
| | 1) THE PROPOSED PROJECT IS CLASSIFIED AS A RENOVATION |
| | PER SECTION 202 FBC-14 ENERGY CONSERVATION. REFER TO |
| | SECTIONS C101.4.3 AND C401.2 AND SUBMIT A COMPLIANCE |
| | REPORT. |
| | |
| | 2) PLEASE PLACE A NOTE ON THE PLAN INDICATING SEPARATE |
| | PERMITS ARE REQUIRED FOR THE HOODS, THE HOOD FIRE |
| | SUPPRESSION SYSTEMS, AND THE WALK-IN COOLERS AND |
| | FREEZERS. PLEASE NOTE THAT A FLORIDA PRODUCT APPROVAL |
| | OR MANUFACTURED BUILDING CERTIFICATION IS REQUIRED FOR |
| | THE EXTERIOR WALK-IN BOX. |
| | |
| | 3) SHEET M1.1: PLEASE LABEL THE RTU'S 1, 2, & 3. |
| | |
| | 4) M1.1: IT APPEARS THAT THE AMOUNT OF CFMS BEING |
| | SUPPLIED ON THE PLAN BY RTU-1 (4110 CFMS) MAY BE |
| | EXCEEDING THE UNIT'S DESIGN AIRFLOW SHOWN IN THE |
| | SCHEDULE. THIS IS ALSO TRUE OF RTU-3 AT 3900 CFMS |
| | |
| | 5) MR1.1: PLEASE VERIFY THAT NO MECHANICAL EQUIPMENT |
| | REQUIRING SERVICING IS WITHIN 10' OF THE ROOF EDGE |
| | UNLESS THE PARAPET WALL AT THAT LOCATION IS MINIMUM 42" |
| | HIGH. OTHERWISE A GUARDRAIL WILL BE REQUIRED- SECTION |
| | 304.11. |
| | |
| | 6) INDICATE HOW ACCESS TO THE EQUIPMENT ON THE ROOF IS |
| | BEING PROVIDED- SEE SECTION 306.5. |
| | |
| | 7) THE OUTDOOR AIR SUPPLY FOR THE RTU'S MUST BE |
| | EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN |
| | THE SYSTEMS OR SPACES ARE NOT IN USE- SECTION |
| | C403.2.4.4 FBC-14 ENERGY CONSERVATION. |
| | |
| | 8) DEMAND CONTROLLED VENTILATION IS REQUIRED IN THE |
| | DINING ROOM PER SECTION C403.2.5.1. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |