| Notes |
| Date |
Text |
| 2017-02-23 08:35:59 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ROOFING SYSTEM THAT WAS SELECTED ON PAGE 26 OF | | | NOA NO. 14-1030.02 HAS A DESIGN PRESSURE OF -52.5 PSF | | | WHICH WILL REQUIRE ENHANCED FASTENING IN THE PERIMETER | | | AND CORNER AREAS. SUBMIT TWO SETS OF SIGNED AND SEALED | | | RAS 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION | | | #7 ON PAGE 30 OF THE NOA. |
|