| Plan Review Notes For Permit 17020971 |
| Permit Number |
17020971 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-03 08:31:28 | | | | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | | ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE SITE PLAN WITH SETBACKS OF GENERATOR AND | | | TANK. | | | 2. IDENTIFY LOCATION OF WINDOWS AND DOORS OF STRUCTURE | | | IN PROXIMITY TO GENERATOR AND TANK. | | | 3. PROVIDE FOUNDATION DETAIL FOR GENERATOR SLAB. | | | 4. PROVIDE ATTACHMENT DETAIL OF GENERATOR TO SLAB. | | | 5. CANNOT VERIFY IF TANK IS ABOVE GROUND OR BELOW | | | GROUND? PROVIDE CLARIFICATION. | | | 6. PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS. | | | 7. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE | | | THEIR PRINTED NAME AND SIGNATURE ON THE SUBMITTED PLANS | | | AND SUPPORTING DOCUMENTS PER FBC 107. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. |
|