Plan Review Notes
Plan Review Notes For Permit 17020966
Permit Number 17020966
Review Stop M
Sequence Number 1
Notes
Date Text
2017-02-24 10:09:131ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020966
 2/24/17
  
 1) THE GARAGE THERMAL ENVELOPE AND MECHANCAL AND
 ELECTRICAL SYSTEMS CANNOT BE EXCLUDED FROM MEETIMNG
 COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION- 2014
 BECAUSE A NEW AC SYSTEM IS BEING INSTALLED TO CONDITION
 THE SPACE. PLEASE NOTE THERE IS NO EXEMPTION UNDER
 SECTION R101.4.8 . IF THE INTENT IS TO DEHUMIDIFY THE
 SPACE THEN PROVIDE A SYSTEM DESIGNED EXCLUISIVELY FOR
 DEHUMIDIFICATION PURPOSES.
  
 2) INDICATE HOW ACCESS WILL BE PROVIDED TO THE FIRST
 FLOOR AIRHANDLERS
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER
 TO VERIFY COMPLIANCE WITH THE NOTE "NOT TO EXCEED 200
 CFM" OF EXHAUST.
  
 4) INDICATE HOW THE KITCHEN HOOD EXHAUST SYSTEM AND O/A
 DCT WILL FUNCTION TOGETHER AND SUBMIT SPECS FOR THE
 HOOD EXHAUST SYSTEM AND MOTORIZED DAMPER-
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  