| 2017-02-24 10:09:13 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17020966 | | | 2/24/17 | | | | | | 1) THE GARAGE THERMAL ENVELOPE AND MECHANCAL AND | | | ELECTRICAL SYSTEMS CANNOT BE EXCLUDED FROM MEETIMNG | | | COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION- 2014 | | | BECAUSE A NEW AC SYSTEM IS BEING INSTALLED TO CONDITION | | | THE SPACE. PLEASE NOTE THERE IS NO EXEMPTION UNDER | | | SECTION R101.4.8 . IF THE INTENT IS TO DEHUMIDIFY THE | | | SPACE THEN PROVIDE A SYSTEM DESIGNED EXCLUISIVELY FOR | | | DEHUMIDIFICATION PURPOSES. | | | | | | 2) INDICATE HOW ACCESS WILL BE PROVIDED TO THE FIRST | | | FLOOR AIRHANDLERS | | | | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER | | | TO VERIFY COMPLIANCE WITH THE NOTE "NOT TO EXCEED 200 | | | CFM" OF EXHAUST. | | | | | | 4) INDICATE HOW THE KITCHEN HOOD EXHAUST SYSTEM AND O/A | | | DCT WILL FUNCTION TOGETHER AND SUBMIT SPECS FOR THE | | | HOOD EXHAUST SYSTEM AND MOTORIZED DAMPER- | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|