| 2017-02-28 12:58:11 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. TWO DRINKING FOUNTAINS ARE REQUIRED. PER FBC PL [B] |
| | 410.2 MINIMUM NUMBER. |
| | WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN |
| | TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE |
| | WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL |
| | COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS. |
| | FBC ACC 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | |
| | 1. THE LAV IN BATHROOM SHALL COMPLY WITH FBC PL 416.5 |
| | TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |