| 2017-03-07 15:02:39 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW |
| | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| | ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| | WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. |
| | 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD |
| | MARKINGS; SEE VERBIAGE IN CODE. |
| | 3. PLEASE SUBMIT REVISED ELECTRICAL CALCULATIONS AT THE |
| | SERVICE AND SHOW THE EXISTING SERVICE CONDUCTOR SIZE. |
| | FBC 107.3.5 |
| | 4. SHOW ON PANEL SCHEDULE AND FLOOR PLAN THE REQUIRED |
| | SHOW WINDOW RECEPTACLES PER NEC 210.62 AND NEC 220.43 |
| | 5. PER NEC 600.5 SHOW THE REQUIRED BRANCH CIRCUIT FOR |
| | SIGNAGE AND REFLECT ON PANEL SCHEDULE. FBC 107.3.5 |
| | 6. PROVIDE AND LABEL THE DRINKING FOUNTAIN WITH GFCI |
| | PROTECTION TO BE READILY ACCESSIBLE (AT THE PANEL |
| | BOARD). NEC 422.52 |
| | 7. LABEL THE RISER DIAGRAM MAINS, 1 OF 4, 2OF 4 TO |
| | COMPLY WITH NEC 230.2E, IDENTIFICATION. |
| | 8. ADDRESS FIRE, BUILDING AND PLUMBING RELATED TO THE |
| | ELECTRICAL SCOPE OF WORK. |
| | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |