| 2017-03-07 08:31:28 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS | | | FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5 | | | 2. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE | | | PER FBC RES E3609.3 | | | 3. PLEASE PROVIDE A GENERAL NOTE FOR WALL SPACE | | | RECEPTACLE REQUIREMENTS PER FBC RES E3901.2.2, 1. ANY | | | SPACE THAT IS 2FT OR MORE IN WIDTH. | | | 4. KITCHEN COUNTERTOPS SPACING TO BE ADDRESSED, | | | RECEPTACLES TO LABELED GFCI PROTECTED. FBC RES E3902.6 | | | 5. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO | | | INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS. | | | 6. PLEASE SHOW ON PANELBOARD 20A CIRCUITS REQUIRED FOR | | | DINING ROOM RECEPTACLES AND BATHROOM RECEPTACLES. FBC | | | RES E3703.2 AND 4 | | | 7. UPDATE CODE IN EFFECT TO REFLECT NEC 2011 NOT 2008 | | | AS NOTED. | | | 8. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | | | | | | | | | | |
|