| 2017-07-10 08:09:44 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17020917 |
| | ADD: 7711 S. DIXIE HWY. BEALLS OUTLET |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 312-522-5835 |
| | E-MAIL: [email protected] |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. JULY 10/2017 |
| | ACTION: DENIED. |
| | |
| | 4X FEE NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| | |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | 1) SHEET LS-1 AND ALL A SHEETS ARE COPIES OF PLANS |
| | SIGNED AND SEALED ELECTRONICALLY AND THEN PRINTED |
| | OUT!!!!!!! PLEASE NOTE ALL OF THE MEP AND FIRE ALARM |
| | PLANS ARE ALSO PAPER FORMS OF AN ELECTRONIC |
| | SIGNATURE!!!! |
| | |
| | IF THE PLANS WERE ORIGINALLY SENT TO US ELECTRONICALLY |
| | THEN WE WOULD ACCEPT THE ELECTRONIC SIGNATURE, BUT ONCE |
| | THE PLANS ARE PRINTED AND SUBMITTED TO THE BUILDING |
| | DEPARTMENT WE HAVE LOST THE ABILITY TO ENSURE THEY |
| | ELECTRONIC SIGNAURE IS REAL. !!!!! |
| | ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005 |
| | (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN |
| | AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST |
| | DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD |
| | PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012, |
| | WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE |
| | BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE |
| | S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE |
| | INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP |
| | S/FIPS180-4/FIPS-180-4.PDF. |
| | |
| | |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEES SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) CORRECTED. |
| | |
| | |
| | 3A) BUILDING PROVISO. 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT |
| | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | 3B) BUILDING PROVISO: 2014 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 3C) BUILDING PROVISO: FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | |