| Notes |
| Date |
Text |
| 2017-05-30 10:20:26 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17020917 | | | 5/30/17 | | | | | | RESULTS: DENIED. | | | | | | 1) THE SUBMITTED ENERGY EFFICIENCY FORM C402-2014 | | | CANNOT BE USED TO SHOW COMPLAINCE FOR AN ADDITION, OR A | | | NEW CONDITIONED SPACE UNLESS THE VALUES FOR THE | | | REQUIRED AND INSTALLED ENVELOPE COMPONENTS AND BUILDING | | | SYSTEMS ARE ENTERED IN THE EFFICIENCY COLUMNS- N/A | | | CANNOT BE ENTERED IN PLACE OF THESE VALUES. PLEASE NOTE | | | THAT THE PERFORMANCE COMPLIANCE OPTION USING THE | | | | | | ENERGYGAUGE SOFTWARE MAY BE USED TO SHOW COMPLIANCE- | | | SEE SECTION C101.5.1 FBC-14 ENERGY CONSERVATION. | | | | | | 2) DEMAND CONTROLLED VENTILATION IS REQUIRED FOR THE | | | SALES AREA IN ACCORDANCE WITH SECTION C403.2.5.1. | | | PLEASE REVISE THE PLAN TO SHOW COMPLIANCE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|