2017-02-28 17:06:591ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020917
 2/28/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) THE PREVIOUSLY UNCONDITIONED STORAGE AND RECEIVING
 AREA THAT IS NOW BEING CONDITIONED MUST BE IN
 COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION
 CODE-2014. REFER TO SECTIONS C101.4.3 AND C401.2 AND
 PROVIDE DOCUMENTATION OF COMPLIANCE. PLEASE NOTE THIS
 NEWLY CONDITIONED AREA IS CLASSIFIED AS AN ADDITION PER
 SECTION C202.
  
 3) SHEET M-1: CLARIFY THE SCOPE OF WORK FOR THE RTU'S.
 THE NOTES INDICATE BOTH EXISTING AND BEING REPLACED.
  
 4) INDICATE HOW ACCESS IS BEING PROVIDED TO THE RTU'S-
 SEE SECTION 306.5.
  