| 2017-02-28 17:06:59 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17020917 | | | 2/28/17 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) THE PREVIOUSLY UNCONDITIONED STORAGE AND RECEIVING | | | AREA THAT IS NOW BEING CONDITIONED MUST BE IN | | | COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION | | | CODE-2014. REFER TO SECTIONS C101.4.3 AND C401.2 AND | | | PROVIDE DOCUMENTATION OF COMPLIANCE. PLEASE NOTE THIS | | | NEWLY CONDITIONED AREA IS CLASSIFIED AS AN ADDITION PER | | | SECTION C202. | | | | | | 3) SHEET M-1: CLARIFY THE SCOPE OF WORK FOR THE RTU'S. | | | THE NOTES INDICATE BOTH EXISTING AND BEING REPLACED. | | | | | | 4) INDICATE HOW ACCESS IS BEING PROVIDED TO THE RTU'S- | | | SEE SECTION 306.5. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|