| 2017-03-01 15:36:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) |
| | SHEET A 1 - THERE APPEARS TO BE A DISCREPANCY IN THE |
| | INDICATED OCCUPANCY LOAD CALCULATIONS RELATING TO THE |
| | LOUNGE, THE TOTAL OCCUPANCY AND THE EXIT WIDTHS. |
| | |
| | PER THE FFPC, 5TH EDITION, CHAPTER 7, MEANS OF EGRESS, |
| | THE LOUNGE IS CONSIDERED AN ASSEMBLY SPACE AND SUBJECT |
| | TO AN OCCUPANCY CALCULATION OF 15/SQ FT. |
| | |
| | ADDITIONALLY, PLEASE REVIEW THE DOOR SCHEDULE DOOR |
| | WIDTHS AND PROVIDE ACCURATE EXIT OPENING WIDTHS TO |
| | ENSURE ADAQUATE EXIT CAPACITY. THE SLIDING DOORS MAY |
| | NOT PROVIDE ADAQUATE WIDTHS IF THEY DO NOT OPERATE AND |
| | THE EMEERGENCY FORCE OPEN IS APPLIED. |
| | |
| | PLEASE REVIEW, CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 2) |
| | SHEET A 1 - THERE IS NO INDICATIONS IF THE OCCUPANCY |
| | WILL BE OPEN RTO THE PUBLIC DURING CONSTRUCTION |
| | ACTIVITY. PLEASE INDICATE INTENTIONS AND IF TO REMIN |
| | OPEN PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING HOW |
| | ALL EXITS WILL BE MAINTAINED (PHASES), FIRE ALARM, AND |
| | FIRE SPRINKLER SYSTEMS WILL BE FUNCTIONAL. |
| | |
| | PLEASE REVIEW AND CLARIFY WITH DETAILS. |
| | |
| | |
| | |
| | 3) |
| | SHEET A 4 - THERE ARE NO DIMENSIONS INDICATED ON THE |
| | PLAN FOR THE TAPE ON THE FLOOR SHOWING ISLES. |
| | |
| | PER NFPA 101, |
| | |
| | 36.2.5.4 AISLES LEADING TO EACH EXIT SHALL BE REQUIRED, |
| | AND THE AGGREGATE WIDTH OF SUCH AISLES SHALL BE NOT |
| | LESS THAN THE REQUIRED WIDTH OF THE EXIT. |
| | |
| | 36.2.5.5 REQUIRED AISLES SHALL BE NOT LESS THAN 36 IN. |
| | (915 MM) IN CLEAR WIDTH. |
| | |
| | PLEASE REVIEW AND CLARIFY OR CORRECT. |
| | |
| | |
| | 4) |
| | SHEET A 4 - THERE IS NO INDICATION OF ISLE TAPE FOR |
| | REAR EXIT PATH LEADING TO VESTIBULE # 1. |
| | |
| | 36.2.5.4 AISLES LEADING TO EACH EXIT SHALL BE REQUIRED, |
| | AND THE AGGREGATE WIDTH OF SUCH AISLES SHALL BE NOT |
| | LESS THAN THE REQUIRED WIDTH OF THE EXIT. |
| | |
| | 36.2.5.5 REQUIRED AISLES SHALL BE NOT LESS THAN 36 IN. |
| | (915 MM) IN CLEAR WIDTH. |
| | |
| | PLEASE REVIEW AND CLARIFY OR CORRECT. |
| | |
| | |
| | |
| | 5) |
| | SHEETS A 8.2 & 8.4 - THERE IS NO INDICATION OF THE |
| | REQUIRED LIGHTWEIGHT ROOF SIGN. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | PLEASE PROVIDE AN INDICATION FOR A "R" SIGN |
| | |
| | |
| | |
| | 6) |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | |
| | 7) |
| | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| | OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |