2017-03-01 15:36:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 SHEET A 1 - THERE APPEARS TO BE A DISCREPANCY IN THE
 INDICATED OCCUPANCY LOAD CALCULATIONS RELATING TO THE
 LOUNGE, THE TOTAL OCCUPANCY AND THE EXIT WIDTHS.
  
 PER THE FFPC, 5TH EDITION, CHAPTER 7, MEANS OF EGRESS,
 THE LOUNGE IS CONSIDERED AN ASSEMBLY SPACE AND SUBJECT
 TO AN OCCUPANCY CALCULATION OF 15/SQ FT.
  
 ADDITIONALLY, PLEASE REVIEW THE DOOR SCHEDULE DOOR
 WIDTHS AND PROVIDE ACCURATE EXIT OPENING WIDTHS TO
 ENSURE ADAQUATE EXIT CAPACITY. THE SLIDING DOORS MAY
 NOT PROVIDE ADAQUATE WIDTHS IF THEY DO NOT OPERATE AND
 THE EMEERGENCY FORCE OPEN IS APPLIED.
  
 PLEASE REVIEW, CORRECT OR JUSTIFY.
  
  
  
 2)
 SHEET A 1 - THERE IS NO INDICATIONS IF THE OCCUPANCY
 WILL BE OPEN RTO THE PUBLIC DURING CONSTRUCTION
 ACTIVITY. PLEASE INDICATE INTENTIONS AND IF TO REMIN
 OPEN PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING HOW
 ALL EXITS WILL BE MAINTAINED (PHASES), FIRE ALARM, AND
 FIRE SPRINKLER SYSTEMS WILL BE FUNCTIONAL.
  
 PLEASE REVIEW AND CLARIFY WITH DETAILS.
  
  
  
 3)
 SHEET A 4 - THERE ARE NO DIMENSIONS INDICATED ON THE
 PLAN FOR THE TAPE ON THE FLOOR SHOWING ISLES.
  
 PER NFPA 101,
  
 36.2.5.4 AISLES LEADING TO EACH EXIT SHALL BE REQUIRED,
 AND THE AGGREGATE WIDTH OF SUCH AISLES SHALL BE NOT
 LESS THAN THE REQUIRED WIDTH OF THE EXIT.
  
 36.2.5.5 REQUIRED AISLES SHALL BE NOT LESS THAN 36 IN.
 (915 MM) IN CLEAR WIDTH.
  
 PLEASE REVIEW AND CLARIFY OR CORRECT.
  
  
 4)
 SHEET A 4 - THERE IS NO INDICATION OF ISLE TAPE FOR
 REAR EXIT PATH LEADING TO VESTIBULE # 1.
  
 36.2.5.4 AISLES LEADING TO EACH EXIT SHALL BE REQUIRED,
 AND THE AGGREGATE WIDTH OF SUCH AISLES SHALL BE NOT
 LESS THAN THE REQUIRED WIDTH OF THE EXIT.
  
 36.2.5.5 REQUIRED AISLES SHALL BE NOT LESS THAN 36 IN.
 (915 MM) IN CLEAR WIDTH.
  
 PLEASE REVIEW AND CLARIFY OR CORRECT.
  
  
  
 5)
 SHEETS A 8.2 & 8.4 - THERE IS NO INDICATION OF THE
 REQUIRED LIGHTWEIGHT ROOF SIGN.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PLEASE PROVIDE AN INDICATION FOR A "R" SIGN
  
  
  
 6)
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 7)
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
  
  