| Notes |
| Date |
Text |
| 2017-03-02 12:27:25 | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | EXISTING ELECTRIC SERVICE. NEC 110.9, 110.10 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | | MEANS. NEC 110.16, 110.22, 110.24 | | | | | | PROVIDE INTERIOR LIGHTING CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY | | | CONSERVATION REQUIREMENTS. FBC C405 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6654 | | | 561-373-3701 | | | [email protected] | | | |
|