Plan Review Notes
Plan Review Notes For Permit 17020901
Permit Number 17020901
Review Stop E
Sequence Number 1
Notes
Date Text
2017-02-22 11:56:37INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PROVISO COMMENTS:
  
 1. PLEASE PROVIDE DATA SHEETS FOR HANDRAIL LIGHTING AND
 ASSOCIATED SELECTED DRIVERS WATTAGE RATED FOR EXTERIOR
 INSTALLATION(WP) TO CONFORM WITH NEC 110.3B
 2. SHOW ON PLANS THE LOCATION OF THE DRIVERS AND WIRING
 METHODS TO HANDRAIL. FBC 107.3.5
 3. REFERENCE TO ELECTRICAL SHEETS ON MASTER PLANS
 SHOWING THE CIRCUIT NUMBERS TO EACH HANDRAIL LOCATION.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  