| Plan Review Notes For Permit 17020814 |
| Permit Number |
17020814 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-03 07:22:03 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS SPECIFY THAT THE TWO SPEED HAYWARD | | | SP2615X202S POOL PUMP HAS A MAXIMUM FLOW RATE OF 122 | | | GPM. THE WATER VELOCITY WILL EXCEED 8 FEET PER SECOND | | | WITH THE 2" MAIN DRAIN SUCTION PIPE SPECIFIED ON THE | | | PLANS. FBC-R4501.6.3 | | | |
|