| Plan Review Notes For Permit 17020803 |
| Permit Number |
17020803 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-05-19 12:20:50 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17020803 | | | 5/19/17 | | | | | | RESULTS: DENIED. | | | | | | 1) THE SUBMITTALS FOR THE 6000 GALLON DIESEL TANK, THE | | | FUEL PIPING, AND DISPENSERS DO NOT MATCH THE PRODUCTS | | | CALLED OUT ON SHEETS G-1.0 & G-2.0. PLEASE PROVIDE | | | SUBMITTALS THAT MATCH OR CORRECT THE PLANS. ALL | | | SUBMTTALS SHALL BEAR THE SHOP DARWING APPROVAL STAMP | | | AND SIGNATURE BY THE ENGINEER OF RECORD. | | | | | | 2) SHEET G-1.0: THE PLANS INDICATE TWO10K GALLON FUEL | | | TANKS TO REMAIN, HOWEVER THE SUBMITTED CONTRACT | | | INDICATE TWO 15K GALLON TANKS TO BE INSTALLED- PLEASE | | | CLARIFY THE SCOPE OF THE PROJECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|